Application
The C-TOP control unit with the AS-i (Actuator Sensor Interface) communication is designed for automation of valves. This option is available for the valves supplied with C-TOP units (ball valve, butterfly valve, seat valves).
Operating principle
The AS-i is a fieldbus system that allows to connect a network of actuators and sensors (detectors) to a control device of a higher level (Master).
Power supply, one or several master modules, bus cable (preformed cable) and the C-TOP prepared for AS-i connection (special internal card, connection cable, AS-i insulation displacement connector) are necessary to create an AS-i network.
The As-i fieldbus is provided with voltage by a power supply source.
The sensors and electrovalves connected to the fieldbus are controlled by the master module.
Every Master sends the information to the PLC and controls up to 62 units (C-TOP's).
The interconnection is made with a preformed cable. The preformed cable is used for transmitting information as well as a power supply of the electrovlaves and detectors. An AS-i version C-TOP must always be installed with inductive detectors and 24V DC.
The preformed cables and bus cables of the C-TOP's are connected by means of insulation displacement connectors, thus, the cables connecting every C-TOP with the control system are not necessary.
Design and features
AS-i bus offers an easy, fast and economic interconnection of sensors and electrovalves (actuators). It facilitates the assembly and the start-up of the plant as the cabling is considerably reduced. It also reduces the start-up time as well as it helps to avoid possible installation errors.
The C-TOP units can be set up according to the customer’s requirements.
Configuration of solenoid valves
. Single-acting actuation - 1 solenoid valve
. Double-acting actuation - 2 solenoid valves
. Mixproof valve – 3 solenoid valves*
Configuration of detectors
The valve position is detected by means of inductive detectors.
. 1 position (closed or open valve) - 1 detector
. 2 positions (closed and open valve) - 2 detectors
. 3 positions (open valve, closed valve, Mixproof seat cleaning) - 3 detectors*
*Depending on the model
Materials
Base PPO + GF
Cover Transparent PC (standard)
Gaskets EPDM (standard)
Options
External detector (Detection of the seat lift when it cannot be detected inside the C-TOP).
Materials for work under extreme conditions (PSU cover).
Segment with 4 inputs y 4 outputs in AS-i 2.1 (31 slaves).
Technical specifications
Max.working temperature 70 ºC (158 ºF)
Media:
Lubricated compressed air, neutral gases according to DIN ISO 8573-1
Pneumatic connections G1/8" (Ø 6 mm pipe)
Electrical connections:
Cable (2 m) with insulation displacement connector (incluided)
Working pressure 1,5 - 7 bar (22 - 102 PSI)
Air flow 150 Nl
Protection IP 65 / 67 according to EN 60529
Adjustment range 3 - 70 mm
Weight 560 - 640 g
AS-i specifications
As-i card 3.0 compatible with 2.1 master
Voltage supply: 29,5 - 31,6 VDC (via bus. Bus cable not included)
Max.number of C-TOPs 62 units (or slaves)
Connecting cable 2 m
Bus cable 100 m
As-i card max. capacity 3 inputs and 3 outputs (3 solenoid valves and 3 detectors)